The standard first-order model is
$$\tau\frac{dy}{dt} + y = Ku \qquad G(s) = \frac{K}{\tau s + 1}$$
Step response
For a step of size $M$ the output is $y(t) = KM\left(1 - e^{-t/\tau}\right)$.
| Time | $\tau$ | $2\tau$ | $3\tau$ | $4\tau$ | $5\tau$ |
|---|---|---|---|---|---|
| % of final change | 63.2 | 86.5 | 95.0 | 98.2 | 99.3 |
- The response never overshoots.
- The initial slope is $KM/\tau$: if the process kept its initial speed it would finish in exactly one time constant.
- The process "settles" (within 2 %) after about $4\tau$.
Integrating processes
A tank with a pump on the outlet (fixed outflow) has $A\,dh/dt = q_{in} - q_{out}$, so $G(s) = 1/(As)$. A step in inflow gives a ramp in level that never settles. These processes must be controlled.
Use the simulation: set $\theta = 0$, change $\tau$ and watch the gold dot. It always sits at 63.2 % of the final value, one time constant after the step.