This lesson ties the course together on the tank from Lesson 2, which you can operate in the simulation below.
Step 1: open-loop behaviour
Put the simulation in Manual. Step the inlet valve from 50 % to 60 % and estimate $K$ and $\tau$ from the level trend (Lesson 5). Repeat at a different operating level: the parameters change because the tank is nonlinear (Lesson 3).
Step 2: tuning
Use IMC rules (Lesson 10) with your model to choose $K_c$ and $\tau_I$, then switch to Auto.
Step 3: disturbance test
Open the outlet valve from 50 % to 80 %. In Manual the level falls to a new steady state. In Auto the controller opens the inlet valve and brings the level back.
Tight versus averaging level control
- Tight control keeps the level close to the set-point, for example for a reactor where volume sets the residence time. The outflow changes quickly.
- Averaging control lets the level swing inside limits so that the outflow to the next unit changes smoothly. Use a low gain and long integral time. A surge tank exists for this purpose.