Feedforward control
Feedback waits for an error. If a disturbance $d$ can be measured, a feedforward controller can act before the CV moves. For process $G_p$ and disturbance path $G_d$, perfect cancellation needs
$$G_{ff}(s) = -\frac{G_d(s)}{G_p(s)}$$
For FOPDT models this becomes a gain, a lead–lag and a delay. A static feedforward (gain only, $-K_d/K_p$) is often enough. Feedforward is always combined with feedback, which cleans up model errors.
Cascade control
A cascade uses two controllers: the outer (primary) controller sets the set-point of an inner (secondary) controller. Example: a reactor temperature controller (outer) sets the set-point of a jacket temperature or coolant flow controller (inner).
- The inner loop fixes disturbances in the inner part (for example coolant supply pressure) before they reach the outer variable.
- It works best when the inner loop is at least 3–5 times faster than the outer loop.
- Tune the inner loop first with the outer loop in manual, then put the inner loop in cascade and tune the outer loop.