Lesson 7 of 19 · Module 2: Time response analysis

Standard test signals and first-order response

Control System Engineering · EEE2510 · Sessions 13–14 · CO3

By the end of this lesson you can

  • Use step, ramp, impulse and parabolic test inputs
  • Derive the step response of a first-order system
  • Find the time constant from a response

Notes

Standard test signals

Input$r(t)$$R(s)$
Impulse$\delta(t)$$1$
Step$A$$A/s$
Ramp$At$$A/s^2$
Parabolic$At^2/2$$A/s^3$

First-order system

Unity feedback around $G = 1/(Ts)$ gives $\dfrac{C(s)}{R(s)} = \dfrac{1}{Ts + 1}$. For a unit step:

$$c(t) = 1 - e^{-t/T}$$

  • At $t = T$ the output reaches 63.2 % of its final value.
  • Initial slope $= 1/T$.
  • Rise time (10–90 %) $= 2.2T$. Settling time $\approx 4T$ (2 %) or $3T$ (5 %).
  • Unit ramp response: $c(t) = t - T + Te^{-t/T}$, with a steady error of $T$.

Set the dead time to zero in the simulation. Change $\tau$ and check that the gold dot always sits at 63.2 % of the final value.

Lecture

🎬
Lecture video
Coming soon. The recorded lecture for this lesson will appear here.

Try it

Exercises

  1. A first-order system reaches 95 % of its final value in 6 s. Find $T$.
    Show solution
    $1 - e^{-6/T} = 0.95 \Rightarrow 6/T = 3 \Rightarrow T = 2$ s.
  2. Find the steady-state error of $1/(Ts + 1)$ to a unit ramp.
    Show solution
    $e_{ss} = T$, from $c(t) = t - T + Te^{-t/T}$.
  3. A thermometer with $T = 10$ s is put into a bath whose temperature rises at 1 °C/s. What is its lag after a long time?
    Show solution
    $e_{ss} = T \times 1 = 10$ °C below the bath temperature.