$$\frac{C(s)}{R(s)} = \frac{\omega_n^2}{s^2 + 2\zeta\omega_n s + \omega_n^2}, \qquad s_{1,2} = -\zeta\omega_n \pm j\omega_n\sqrt{1-\zeta^2}$$
Damped frequency $\omega_d = \omega_n\sqrt{1-\zeta^2}$. Undamped ($\zeta = 0$), underdamped ($0 < \zeta < 1$), critically damped ($\zeta = 1$), overdamped ($\zeta > 1$).
Time-domain specifications (underdamped, unit step)
| Specification | Formula |
|---|---|
| Rise time $t_r$ (0–100 %) | $\dfrac{\pi - \theta}{\omega_d}$, with $\theta = \cos^{-1}\zeta$ |
| Peak time $t_p$ | $\dfrac{\pi}{\omega_d}$ |
| Peak overshoot $M_p$ | $e^{-\zeta\pi/\sqrt{1-\zeta^2}}\times 100\,\%$ |
| Settling time $t_s$ | $\dfrac{4}{\zeta\omega_n}$ (2 %), $\dfrac{3}{\zeta\omega_n}$ (5 %) |
| Delay time $t_d$ | $\approx \dfrac{1 + 0.7\zeta}{\omega_n}$ |
Added poles and zeros
- An extra left-half-plane pole slows the response and reduces overshoot. If it is more than five times farther from the axis than the dominant poles, it can be ignored.
- An extra left-half-plane zero speeds the response and increases overshoot.